Active stand-alone detection system based on laser technology for the early detection of fires in small areas. The actuation on the loop and the resetting function is carried out via the esserbus transponder (Part No. 808623). Actuation on a conventional line is carried out via the same transponder. The device requires a separate voltage supply of 24 V DC.
Features:
Technical Data:
Operating voltage 18 ... 30 V DC
Quiescent current @ 24 V DC max. approx. 220 mA
Alarm current @ 24 V DC approx. 295 mA
Contact load relay 2 A @ 30 V DC NO/NC
Sensitivity 0.005 % - 20% obs/m
Connection terminal 0.2 ... 2.5 mm²
Maximum tube length 25 m
Area to be monitored 250 m²
Ambient temperature 0 °C ... 40 °C
Air humidity < 95 %
Type of protection IP 30
Weight approx. 2 kg
Specification EN 54-20, Class A, B, C
Dimensions W: 255 mm H: 185 mm D: 90 mm